Sorry, our Site is Built in Flash...

Get Adobe Flash player

If you are looking for something specific, please follow one of these links:

Interactive Guide
Waymarker Warning
Wire Guard
Sovereign Explosion Proof
Phoenix
Sentry Wet Location
Telesis TLXCOM
Telesis CMG
Sovereign
Self Luminous Exit Signs Tritium Q & A
Waymarker Overview
Telesis TLRC
Razor Custom Graphics
Weatherlite
Lucenta
Razor
Lifeline
Sentry Custom Graphics
Evenlite Company Profile
Razor with Remote
Search
Slimline
Telesis TLM2
Tufflite NX
Tufflite DT
Lifeline Custom Graphics
Telesis TMR
Institutional Signs
Waymarker General Safety Signs
Slimline Recessed
Installation Photos
Sentry
Waymarker
RS Security Cover
Tufflite S
Vandal Resistant Shield
Disney Installation Photos
Sentry Recessed
Evenlite Home
Decor DS
Tufflite IX
ISO Footcandle Curves vs. Actual Lighting Conditions
Waymarker Directional Indicators
Sentry With Remote
Haverford College Installation Photos
Contact A Representative
ISO Footcandle Distribution Curves
Lehigh University Installation Photos
Sovereign Custom Graphics
Waymarker Strip
Waymarker Step Marker
Sentry Industrial
Waymarker Door Handle
Marker Lite
Waymarker Tape
Mirror Lite
Aperion
Slimline Vandal Resistant
Terms and Conditions
Contact Us
Tufflite H
Lamp Selection Guide
Lamp Head Selection Guide
Conductor Sizes for Remote Loads
Decor DP
Telesis Exit Signs
Waymarker Extruded Aluminium
Isofootcandle

The NFPA 101 code requires even illuminance, over a specified area, of 1 footcandle average with a minimum illuminance of 0.1 footcandle at any point with a ratio of not more than 40 to 1 maximum to minimum illuminance. To meet this requirement, for Emergency Lighting, several considerations must be taken into account when using Isofootcandle Distribution Curves to determine distances between units.

Isofootcandle Distribution Curves show the illuminance for specified footcandle values at various distances. These curves reflect measurements in ideal conditions with the measuring device normal (90 degrees) to the incoming light. (See Fig. 1)

Fig. 2 shows a 3D illustration of Isofootcandle Distribution Curve No. 25 for a 50 Watt, 12 degree MR16 Lamp. The light pattern for this lamp is symmetrical in horizontal and vertical planes. This curve shows a distance of 112 ft for an illuminance of 1 footcandle. However, when this lamp is lighting a Path of Egress, three factors must be taken into account to determine the number of and spacing of Emergency Lighting Units and the illumination "E" at any point on the floor.

1. The distance "d" from the lamp (the Inverse Square Law)
2. The cosine of angle "0" that the light strikes the floor (Lambert’s Cosine Law)
3. The distance from the center of the beam (Lamps with narrow Beam Angles will fall off rapidly in intensity as the distance increases from the center of the beam)

In Fig. 3 a typical two unit configuration is shown lighting a 3 ft. wide by 65 ft. Long Path of Egress. The lamps are arranged so that the beams overlap producing light under opposite units. This is generally necessary to provide even illumination along the whole length of the path. Small areas can be covered with a single lamp. In this example the large angle "0" results in a cosine of 75 degrees that cuts the illuminance "E" at beam center by 74%. Because of these factors the maximum spacing for this type of lamp to meet NFPA 101 without the benefit of ceiling, wall, or floor reflections is 65 feet or about 30 feet per lamp.

For more information consult the Illuminating Engineering Society of North America Lighting Handbook.